广州蓄能水电厂(Guangzhou Pumped Storage Power Station简称为GPSPS)B厂共装设四台300MW可逆式水轮发电机组,主要担任广东电力系统的调峰、填谷任务,同时兼顾调相和紧急事故备用。电厂水泵和调相工况启动的主要方式为变频器启动,背靠背启动是其备用启动方式。全厂四台机组共用一套静止变频启动装置。本文详细介绍了广蓄B厂静止变频启动装置(Static Frequency Converter简称为SFC)隔离变压器#4冷却风机电源开关跳闸故障原因查找及分析处理,并详细分析了六台冷却风机的启动过程和停机过程。避免隔离变温度高导致SFC跳闸,而引起机组启动失败。以便类似故障发生时可以迅速地查出故障原因并尽快消除故障,尽早恢复静止变频启动装置正常运行。
Guangzhou Pumped Storage Power Station (referred to as GPSPS) B plant a total of four 300MW reversible hydro-generator set, mainly for Guangdong power system peak shaving, filling tasks, taking into account the phase and emergency spare. Power plant pumps and phase modulation conditions start the main way for the inverter to start, back to back start is the standby start mode. The whole plant four units share a set of static frequency start device. This paper introduces the fault finding and analysis of the power switch tripping of Static Fan Converter (Static Frequency Converter for short) converter isolation fan # 4 cooling fan and analyzes the start-up process and shutdown process of the six cooling fans . Avoiding Isolation High temperatures lead to SFC trips that cause the unit to fail to start. So that similar faults can be quickly detected when the cause of the malfunction and eliminate the failure as soon as possible, as soon as possible to restore the static frequency inverter to start the normal operation.