为查明造成阴极保护系统异常的原因,并采取有效的防护措施加以修复,对兰成渝输油管道成县—阳坝段的阴极保护系统进行了全面的综合性检测与评价,揭示了此类地段埋地长输管道阴极保护系统通常存在的问题,并对该类系统的有效修复提出了合理化建议。综合检测的结果表明,造成成县—阳坝段管道自然电位过负,从而导致其间2座阴极保护站不能正常投运的主要原因有3个方面:第一,管道沿线敷设了大量的在役牺牲阳极抬高了管道的阴极保护电位;第二,管道沿线存在大量的隐蔽干扰源,这些干扰源直接构成了对管道的交直流干扰;第三,异常段管道本身存在较多的防腐层破损点,致使交直流干扰电流能够顺利的通过破损点处流入管道,从而抬升了管道的自然电位。
In order to find out the cause of the abnormality of the cathodic protection system and to take effective protective measures to repair it, the comprehensive and comprehensive detection and evaluation of the cathodic protection system of the Chengcheng-Yangba section of the Lancheng-Yu oil pipeline was carried out. Buried long-distance pipeline cathodic protection system usually exist problems, and the effective restoration of such systems put forward reasonable suggestions. The results of the comprehensive test show that there are three main reasons that lead to the natural potential of pipeline in Chengxian-Yangba being negative, which leads to the failure of two cathodic protection stations in operation. There are three main reasons: firstly, a large number of in-service The sacrificial anode elevates the cathodic protection potential of the pipeline. Secondly, there are a large number of hidden sources of interference along the pipeline, which directly constitute the AC-DC interference to the pipeline. Thirdly, there is more damage of the coating in the abnormal section itself Point, resulting in AC and DC interference current can be successfully passed through the damaged point into the pipeline, thereby raising the natural potential of the pipeline.