提出了一种新型的逆流式露点间接蒸发冷却器,研究了进气的相对湿度、温度变化对其冷却(湿球)效率的影响。结果显示:相对湿度和温度的变化对冷却器的冷却(湿球)效率具有显著的影响,较低的相对湿度和温度能获得较高的冷却(湿球)效率,所有运行条件下的冷却(湿球)效率超过100%。当环境温度为303.15K,相对湿度为10%时,冷却器的效率最高为128.5%,表明冷却器具有较好的降温效果;改进后的结构相比较原始结构,进口压力降低1.107%,产气温度降低了0.314K。
A new type of countercurrent dew point indirect evaporative cooler was proposed. The effect of relative humidity and temperature on the efficiency of cooling (wet bulb) was studied. The results show that: the relative humidity and temperature changes have a significant effect on the cooler cooling (wet bulb) efficiency, lower relative humidity and temperature can get higher cooling (wet bulb) efficiency, cooling under all operating conditions Wet bulb) efficiency of more than 100%. When the ambient temperature is 303.15K and the relative humidity is 10%, the maximum efficiency of the cooler is 128.5%, which shows that the cooler has a good cooling effect. Compared with the original structure, the improved structure reduces the inlet pressure by 1.107% Temperature dropped by 0.314K.