论文部分内容阅读
中温冷水机组诱导系统由三部分组成:中温冷水机组、集约型空气处理机组、末端诱导室。集约型空气处理机组采用椭圆管换热技术实现13℃低温送风的同时,将供回水温度提高至10/20℃。对该系统及一次回风系统进行分析,对比结果发现,处理相同房间空气时,中温冷水机组诱导系统的输入比一次回风系统输入少178.28k W,可节能42.29%;中温冷水机组诱导系统的损失比一次回风系统的损失低,两系统对应效率分别为9.49%和5.58%。
Medium temperature chiller induction system consists of three parts: temperature chiller, intensive air handling unit, the end of the induction chamber. Intensive air handling units using oval tube heat transfer technology to achieve 13 ℃ low temperature air supply, while the supply and return water temperature to 10/20 ℃. Analysis of the system and a return air system, the results showed that when the air in the same room was treated, the input of induction system of medium temperature chiller was 178.28kW less than that of the one return air system, saving 42.29% of the energy. Induction chiller system induction system The loss is lower than that of a return air system. The corresponding efficiencies of the two systems are 9.49% and 5.58% respectively.