《高层民用建筑设计防火规范》(GB50045—95)中,明确提出,高位水箱的设置高度应保证最不利点消火栓静水压力,当建筑高度不超过100米时,高层建筑最不利点消火栓静水压力不应低于0.07MPa,当建筑高度超过100米时,高层建筑最不利点消火栓静水压力不应低于0.15MPa,若不能满足上述静压要求时,应设增压设施,多年来,因工程性质,规模大小等特征的不同,增压
“High-rise Civil Building Design Fire Prevention Code” (GB50045-95), clearly stated that the height of the high water tank should ensure that the most adverse point hydrant hydrostatic pressure, when the building height does not exceed 100 meters, the highest point of the high-rise building hydrant hydrostatic pressure is not Should be less than 0.07MPa, when the building height exceeds 100 meters, the hydrostatic pressure of the fire hydrant at the most unfavorable point of the high-rise building shall not be lower than 0.15MPa. If the above static pressure requirements cannot be met, pressurization facilities should be set over the years, due to the nature of the project. , size and other characteristics of different pressurization