根据我台配电房现有的接线方式在运行中存在的不足,依托现有的接线方式,设计一种将其优化的接线——10KV采用单母线分段,0.4KV采用具有备用变压器的环网接线开环运行,以满足电能系统电气接线的可靠性、灵活性等方面的要求。并通过在母线分段开关处增加备自投、在10KV出线开关处增加自动重合闸、在0.4KV配电环节中增加具有备自投功能的联络开关、采用开关设备和馈线终端单元(FTU)等措施,增强配电自动化,以提高我配电系统的可靠性、缩短事故造成的停电时间。
According to the existing connection mode in our power distribution room, there is a shortage in operation. Based on the existing connection mode, a kind of wiring to optimize it is designed - 10KV adopts single busbar section, 0.4KV adopts the ring with spare transformer Network wiring open-loop operation, to meet the electrical system wiring reliability, flexibility and other requirements. And by adding a switch at the bus section switch, an automatic reclosing switch is added at the 10KV outlet switch, a contact switch with automatic switch-on function is added in the distribution section of 0.4KV, the switchgear and the feeder terminal unit (FTU) And other measures to enhance distribution automation to improve the reliability of my distribution system to reduce the power outage caused by the accident.