目的了解深圳地铁一号线地铁站的室内空气质量状况及其影响因素。方法根据《公共场所卫生监测技术规范》的要求,对一号线地铁站的站厅、站台及其室外对照进行卫生监测。结果部分地铁站的室内噪声的监测结果均值达不到卫生标准的要求;站厅的室内照度、CO2高于站台,而站厅的室内甲醛、IP低于站台,差异有统计学意义(p<0.05);站厅的温度、湿度、风速、噪声、CO和空气细菌总数略低于站台。上午监测的温度、湿度、照度、CO2低于下午,而上午监测的甲醛、空气细菌总数高于下午,差异有统计学意义(p<0.05)。结论新风质量和人流量对地铁站室内的空气质量有一定影响。
Objective To understand the indoor air quality of Shenzhen Metro Line 1 and its influencing factors. Methods According to the requirements of “Technical Specifications for Health Monitoring in Public Places”, health monitoring was conducted on the station hall, platform and its outdoor control of Line 1 subway station. Results The monitoring results of indoor noise of some subway stations did not reach the standard of health. The indoor illumination of station hall was higher than that of platform site, while the indoor formaldehyde and IP of station hall was lower than that of platform site (p < 0.05). The temperature, humidity, wind speed, noise, CO and air bacteria in station are slightly lower than the platform. In the morning, the temperature, humidity, illumination and CO2 in the morning were lower than those in the afternoon. The total number of formaldehyde and air bacteria monitored in the morning was higher than that in the afternoon, with a significant difference (p <0.05). Conclusion The fresh air quality and the flow of people have an impact on the indoor air quality of the subway station.