介绍了该装置的应用现状及工作原理。JB/T 11133—2011《水冷冷水机组管壳式冷凝器胶球自动在线清洗装置》提出采用冷凝器端差表征污垢热阻,冷凝器端差增加量应不大于0.3℃±0.1℃,并给出了部分负荷时端差增量的折算方法。
The application status and working principle of the device are introduced. JB / T 11133-2011 “On-line automatic cleaning device of water-cooled chiller shell-and-tube condenser glue ball” proposed to use the terminal temperature difference to characterize the fouling resistance. The increase of condenser terminal temperature difference should not exceed 0.3 ℃ ± 0.1 ℃ Out of the partial load when the delta method of conversion.