论文部分内容阅读
今年3月13日下午,江苏省盱眙县化肥厂碳化车间清洗塔上一根φ38mm的测温套管与法兰连接处严重漏气,厂领导要求在不停机、不减压的条件下采取临时堵漏措施,操作工第一次用铁卡和橡胶板堵漏失败。下午17时许,在厂领导的再次要求下,操作工用平车内胎橡皮企图包住泄漏处。当时,塔内的压力较高,高速喷出的氢气与橡胶皮摩擦产生静电火花而突然起火,一名职工当场破烧死,另一名受重伤的工人也于3月23日死亡,火灾造成直接经济损失34万余元。 这起火灾的直接原因是高速喷出的氢气与橡胶皮摩擦产生静电的
On the afternoon of March 13 this year, a φ38mm thermowell and a flange connection were found on the washing tower of the Chemical Plant of Xuyi County, Jiangsu Province, causing severe gas leaks. The factory leaders requested temporary non-stop and non- Plugging measures, the first time the operator plugged with iron and rubber plates failed. At 17 o’clock in the afternoon, under the leadership of the factory, the operator attempted to enclose the leak with an inner rubber tire. At that time, the tower of higher pressure, high-speed discharge of hydrogen and rubber skin friction sparks and suddenly sparked a fire broke down on the spot, another seriously injured workers were killed on March 23, the fire caused Direct economic losses of 340,000 yuan. The direct cause of the fire is high-speed discharge of hydrogen and rubber skin friction produce static electricity