1982年8月,河南商丘地区建委在工会办公楼工地检查工程质量时,发现了一批没有型号和制作日期标志的预应力混凝土多孔板。这种构件,既用在楼面上,又用在屋面上。楼面和屋面的设计荷载往往是不一样的,若错用了多孔板,会因受力主钢筋不足,引起楼板断裂,进而造成房屋倒塌事故的发生。这个情况引起了建委的警觉,随即组织设计、施工、建设等单位的有关工程技术人员,对该工程进行了认真检查。这是一幢三层的砖混结构,建筑面积1347米~2。该楼房除用作办公外,还设有乒乓球室、教室、会议室等,其中会议室的开间是4.2米,跨度6.6米,二、三层楼面设计用420×60×11cm的二级预应力钢筋混
In August 1982, when the construction committee of the Shangqiu District of Henan Province inspected the quality of the work in the office building of the trade unions, it discovered a number of prestressed concrete perforated plates that were not marked with the type and date of manufacture. This kind of structure is used both on the floor and on the roof. The design load of the floor and the roof is often different. If the perforated plate is misused, the main reinforcement of the force will be insufficient and the floor will be broken, which will cause the collapse of the house. This situation has aroused the vigilance of the Construction Committee. The relevant engineering and technical personnel of the organization’s design, construction, and construction units were then carefully examined. This is a three-story brick-concrete structure with a building area of 1347 m~2. In addition to the office building, the building also has a table tennis room, a classroom, a conference room, etc. The opening of the conference room is 4.2 meters with a span of 6.6 meters. The second floor and the third floor are designed with a secondary level of 420*60*11 cm. Prestressed steel reinforcement