在对一栋满足节能65%设计标准的住宅进行逐时能耗分析的基础上,得出间歇运行的最大热负荷约为连续运行时的3倍,但是连续运行和间歇运行的累计耗热量分别为39.4 kW·h/(m~2·a)和33.6kW·h/(m~2·a),建议地源热泵尽量采用连续运行的方式。分析实际项目的装机容量和土壤温度逐年变化情况,所调研的住宅1第一年土壤计算温降为1.81℃,实际温降为1.9℃。提出为了避免土壤温度逐年降低,可采用具有分区补热功能的跨季节蓄热空气源-土壤源复合式系统。
On the basis of hourly energy consumption analysis of a house meeting the design standard of 65% energy saving, the maximum heat load of intermittent operation is about 3 times of continuous operation, but the cumulative heat consumption of continuous operation and intermittent operation respectively Is 39.4 kW · h / (m ~ 2 · a) and 33.6 kW · h / (m ~ 2 · a), it is suggested that the source heat pump adopt continuous operation as much as possible. Analysis of the actual project capacity and soil temperature changes year by year, the first study of residential soil temperature calculated 1.81 ℃, the actual temperature drop of 1.9 ℃. In order to avoid the year-by-year decrease of the soil temperature, a cross-season regenerative air source-soil source composite system with the function of zonal heating can be adopted.