徐塘发电厂装有二台SG-480/46型锅炉,其低温段过热器是单回路,蒸汽流速为13.7米/秒。由于蒸汽流速较低,管壁对蒸汽的放热系数小,当锅炉负荷超过3.5万瓩时,低温段过热器经常超温,严重影响了锅炉的安全运行。为此,徐塘发电厂将单回路改为双回路,具体方案如下:将低温段过热器原来的出口联箱改为中间联箱,另加两只小联箱,作为低温段过热
Xu Tong Power Plant is equipped with two sets of SG-480/46 boiler, the low temperature superheater is a single loop, the steam flow rate of 13.7 m / s. Due to the low steam velocity, the heat release coefficient of the wall to the steam is small. When the boiler load exceeds 35,000 瓩, the superheater in the low temperature section often over-temperature, seriously affecting the safe operation of the boiler. To this end, Xu Tong Power Plant will be a single loop into a double loop, the specific program is as follows: the low temperature superheater original export header box to the middle of the header, plus two small header, as the low temperature overheating