针对西寺坪电站在甩负荷后转至孤网运行过程中,出现的多台机组成组调节过程中振荡过速的情况,研究了调速器比例—积分—微分(PID)控制模型,找出了事故原因,提出了调速器程序及参数的处理方法,认为当系统频率大于52Hz时,若PID比例项的增量输出大于0,将PID比例项的增量输出清零;当系统频率小于48Hz时,若PID比例项的增量输出小于0,亦将PID比例项的增量输出清零;当系统频率介于48~52 Hz之间时,正常PID调节。之后通过现场试验验证了修改后调速器的性能。结果表明,修改后调速器调节性能反应良好。研究结果为相似运行方式条件下的多机组成组调节提供借鉴。
Aiming at the situation that the Xisiping power station oscillates too fast during the regulation of multiple units during the transition to isolated grid after load rejection, the proportional-integral-derivative (PID) control model of the governor is investigated to find out According to the reason of the accident, the governor program and parameter processing method are put forward. When the system frequency is greater than 52Hz, if the incremental output of PID proportional term is greater than 0, the incremental output of PID proportional term is cleared. When the system frequency is less than 48Hz, if the incremental output of PID proportional term is less than 0, the incremental output of PID proportional term will also be cleared; when the system frequency is between 48 and 52 Hz, the normal PID will be adjusted. After the field test to verify the modified governor performance. The results show that the modified governor performance is good. The research results provide references for adjusting the multi-unit grouping under the similar operation mode.