摘 要:10kV配电变压器应用于10kV配电网络中,其油浸式变压器过载能力较强,绝缘性能和散热能力优于其他类型的变压器,但配电变压器在运行以后,其维护工作跟不上来,导致故障性的缺陷,不能及时消除,久而久之造成损坏;本文以长葛10kV配网近年来配电变压器运行情况和配变故障情况、故障类型的统计数据,以配电变压器运行规程为技术支撑,结合工作实践经验,逐步摸索出一套实用的维护方法,效果良好,对提高配电变压器可靠、安全、经济运行,保障配电变压器在设计的寿命周期,应用有着现实性的意义。
关键词:配电变压器 ;安全运行 ; 故障;缺陷 ; 维护
中图分类号:TM421文献标识码: A
Abstract:: the 10kV distribution transformer used in 10kVdistribution network, the oil immersed transformer overload ability, insulating transformer performance andheat dissipation is superior to other types, but thedistribution transformer in operation, the maintenance work to keep up, leading to defects in nature, can not be eliminated in time, the damage in the course of time;taking Changge 10kV the distribution statistics of distribution transformer operation and distribution of fault type, fault in recent years, the operation rules of distribution transformer for technical support, combined with practical work experience, and gradually worked out a set of practical maintenance methods, good effect, to improve the reliability, security, distribution transformereconomic operation, protection of distribution transformerin life cycle design, has the practical significance of application.
Keywords: distribution transformers; safety; faultmaintenance; defect
中图分类号:TM421文献标识码:A
1.引言
长葛属于温带季风气候特征,特点是高温多雨,长葛市10kV配网运行的配电变压器多为S9型S11型的油浸式变压器;最近几年来,我公司公用配电变压器、用户变压器因失修损坏的问题十分突出,针对配电变压器运行状况、故障类型进行了调研和统计分析。
2.配电变压器运行中存在主要问题及解决方法
(1)配电变压器高低压侧熔丝与容量匹配的问题
配电变压器高压跌落式熔断器的熔丝容量选择得过大,还有用铝丝代替熔丝的,从某种意义上来讲,完全丧失了保护配电变压的作用。一旦配电變压器出现内部故障或配电线路出现短路故障,就会因保险熔丝不合格对变压器的内绝缘造成损伤,或因无保险丝而使变压器烧坏。由这种原因造成配电变压器损坏的最多。解决的办法是在配电变压器的高低压侧必须安装与配电变压器容量相匹配的熔丝,高压侧跌落保险中装设的熔丝,主要作用是变压器内部或高压引线等出现故障时保护,其容量为高压侧2Ie;低压侧配置的熔丝,主要作用是配电变压器长时间过载运行或低压侧短路保护,其容量为低压侧1.2-1.5Ie。正确配置熔丝,不但能够对配电变压器起到保护的作用,还能够防止变压器超容量运行。
(2)绕组绝缘电阻值过低
配电变压器长期高温或超容量运行,油质劣化就非常快,油的粘稠度变大,内循环速度降低,变压器的散热不好,温升增高,加速油质的劣化。劣化后的油酸性增强,使配电变压器整体、绕组的绝缘性能降低,继续漫延其绝缘受到破坏。针对油质是否出现劣化,做好的工作有:一是定期查看油位计油的颜色、如果由初期的淡黄色逐步变成橙色,棕色,且油的粘度增大,则表明变压器油已经劣化,必须更换变压器油。二是定期测量绕组的绝缘电阻,用兆欧表对绕组的绝缘电阻进行测量,参照《电气设备预防性试验规程》10kV/0.4kV配电变压器绝缘电阻的要求,判断绕组的绝缘电阻是否下降,如果不合格,则应安排对变压器进行大修。
(3)配变三相负荷不平衡,偏相长期超负荷运行。
配电变压器偏相长期满载或超载运行,如果三相不平衡率≥40%。将导致变压器过热,绝缘油老化, 降低绕组绝缘性能。解决的措施: 一是查看配电变压器运行时的三相电流是否一致,若是某一相或两相电流高于另外一相或两相,对用电设备采取改接的方式来平衡三相负荷,在平衡的条件下运行。二是要及时给变压器增容,避免变压器长期过负荷运行而受到损坏。
(4)配电变压器日常维护工作
一是配电变压器清洁工作,配电变压器一般安装于户外,变压器器身,高低压瓷瓶落有灰尘等杂质,其瓷绝缘的泄漏电流增大。必须对配电变压器的器身、瓷套管定期擦试,保持清洁。二是要经常检查变压器的吸湿器内硅胶是否变色,如有变色要及时更换,防止绕组受潮。三是对调档开关、大盖、瓷套管的根部检查有无渗漏油的缺陷,如果有油灰,要对其螺丝进行对称性地紧固,并将油灰清理干净。四是如发现油位下降,必须对变压器及时补油。五是检查接地连接的可靠性,如果出现松动,必须对其紧固。六是检查高、低压的接线连接是否牢靠,如果出现变色,局部过热,应立即对变压器停止运行,在做好安全措施后,进行紧固。七是分相检查运行中配电变压器的三相电压,是否在额定电压值的范围内运行,如果电压偏低,应将无功补偿的电容器投入运行,或是调整变压器的分接开关的档位。八是经常对变压器的温度表进行查看,变压器运行温度是否过高,如果温度过高,应采取给变压器降温或限负荷的方法。
(5)接地电阻超标,遭受雷击。
配电变压器雷击损坏主要原因是由于避雷器失效或接地不良而引起的,必须在配电变压器的高、低压侧配置合格的避雷器;一是定期测量避雷器接地电阻,R地≤4Ω,超标及时整改。二是每年雷雨季节前,要安排避雷器的试验,若是试验不合格者,应立即更换。
3.配电变压器运行工况监督方法
运行中的配电变压器,用“看、测、听、闻”这四种方法
(1)“看”的方法
①“看”变压器的大盖、套管、油位计、排油阀、分接开关等,其密封的良好性,有无渗漏油现象。高、低压瓷套管有无裂纹和放电闪络的痕迹。
②“看”油位和油色:油位是否正常。如偏高,变压器运行带负荷后,随着油温的上升,油从油枕的呼吸器处溢出;如偏低,对变压器的绝缘和散热作用会降低,变压器可靠运行受到影响,缺油量较大时变压器会被烧坏。再“看”油有没有变颜色,如果颜色变重了,则需要更换变压器油了。
(2)“测”量(试)的方法
①“测”量变压器绕组对地绝缘电阻和绕组间的绝缘电阻(选用1000~2500V兆欧表),应符合表—2的规定:
②“测”量变压器的接地电阻、避雷器的接地电阻,其阻值在规定的范围内。
(3)“听”的方法
用一节绝缘操作棒一端接触配电变压器的外壳,在另一端用耳听变压器运行中的声音:
①“听”到变压器发出均匀且连续 “嗡嗡”的声音,这是交流电通过线圈时产生的电磁力吸引硅钢片与变压器自身的振动而发出的响声,变压器运行正常。。
②“听”到变压器发出“啾、啾、啾”的声音,有时还造成高压熔丝熔断,这是分接开关未到位,应停电把分接开关重合到位。
③“听”到变压器发出的“嗡嗡”声音忽高忽低,无其它杂音,这是变压器过载运行引起的。应采取限制负荷的方法,保证配电变压器在规定的负荷范围内运行;若是负荷增长了,应考虑配电变压器增容。
④“听”到变压器发出“轰轰”声音,这常是因变压器低压侧的架空线发生接地引起的。
(4)“闻”是靠人的嗅觉功能,“闻”运行中的变压器及周围,有无烧皮子的味道或其他异味,若有异常的味道,必须查清异味的来源。
4.结束语
配电变压器安全、可靠、经济且长周期运行,是与精心维护工作分不开的,定期维护是保证变压器稳定运行的基本保障,避免配电变压器烧毁事故的发生。
参考文献:
[1]芮静康《现代工业与民用供配电设计手册》中国水利水电出版社 2004年
[2]钟洪璧 高占邦 王正官等《电力变压器检修与试验手册》中国电力出版社 2000.1
关键词:配电变压器 ;安全运行 ; 故障;缺陷 ; 维护
中图分类号:TM421文献标识码: A
Abstract:: the 10kV distribution transformer used in 10kVdistribution network, the oil immersed transformer overload ability, insulating transformer performance andheat dissipation is superior to other types, but thedistribution transformer in operation, the maintenance work to keep up, leading to defects in nature, can not be eliminated in time, the damage in the course of time;taking Changge 10kV the distribution statistics of distribution transformer operation and distribution of fault type, fault in recent years, the operation rules of distribution transformer for technical support, combined with practical work experience, and gradually worked out a set of practical maintenance methods, good effect, to improve the reliability, security, distribution transformereconomic operation, protection of distribution transformerin life cycle design, has the practical significance of application.
Keywords: distribution transformers; safety; faultmaintenance; defect
中图分类号:TM421文献标识码:A
1.引言
长葛属于温带季风气候特征,特点是高温多雨,长葛市10kV配网运行的配电变压器多为S9型S11型的油浸式变压器;最近几年来,我公司公用配电变压器、用户变压器因失修损坏的问题十分突出,针对配电变压器运行状况、故障类型进行了调研和统计分析。
2.配电变压器运行中存在主要问题及解决方法
(1)配电变压器高低压侧熔丝与容量匹配的问题
配电变压器高压跌落式熔断器的熔丝容量选择得过大,还有用铝丝代替熔丝的,从某种意义上来讲,完全丧失了保护配电变压的作用。一旦配电變压器出现内部故障或配电线路出现短路故障,就会因保险熔丝不合格对变压器的内绝缘造成损伤,或因无保险丝而使变压器烧坏。由这种原因造成配电变压器损坏的最多。解决的办法是在配电变压器的高低压侧必须安装与配电变压器容量相匹配的熔丝,高压侧跌落保险中装设的熔丝,主要作用是变压器内部或高压引线等出现故障时保护,其容量为高压侧2Ie;低压侧配置的熔丝,主要作用是配电变压器长时间过载运行或低压侧短路保护,其容量为低压侧1.2-1.5Ie。正确配置熔丝,不但能够对配电变压器起到保护的作用,还能够防止变压器超容量运行。
(2)绕组绝缘电阻值过低
配电变压器长期高温或超容量运行,油质劣化就非常快,油的粘稠度变大,内循环速度降低,变压器的散热不好,温升增高,加速油质的劣化。劣化后的油酸性增强,使配电变压器整体、绕组的绝缘性能降低,继续漫延其绝缘受到破坏。针对油质是否出现劣化,做好的工作有:一是定期查看油位计油的颜色、如果由初期的淡黄色逐步变成橙色,棕色,且油的粘度增大,则表明变压器油已经劣化,必须更换变压器油。二是定期测量绕组的绝缘电阻,用兆欧表对绕组的绝缘电阻进行测量,参照《电气设备预防性试验规程》10kV/0.4kV配电变压器绝缘电阻的要求,判断绕组的绝缘电阻是否下降,如果不合格,则应安排对变压器进行大修。
(3)配变三相负荷不平衡,偏相长期超负荷运行。
配电变压器偏相长期满载或超载运行,如果三相不平衡率≥40%。将导致变压器过热,绝缘油老化, 降低绕组绝缘性能。解决的措施: 一是查看配电变压器运行时的三相电流是否一致,若是某一相或两相电流高于另外一相或两相,对用电设备采取改接的方式来平衡三相负荷,在平衡的条件下运行。二是要及时给变压器增容,避免变压器长期过负荷运行而受到损坏。
(4)配电变压器日常维护工作
一是配电变压器清洁工作,配电变压器一般安装于户外,变压器器身,高低压瓷瓶落有灰尘等杂质,其瓷绝缘的泄漏电流增大。必须对配电变压器的器身、瓷套管定期擦试,保持清洁。二是要经常检查变压器的吸湿器内硅胶是否变色,如有变色要及时更换,防止绕组受潮。三是对调档开关、大盖、瓷套管的根部检查有无渗漏油的缺陷,如果有油灰,要对其螺丝进行对称性地紧固,并将油灰清理干净。四是如发现油位下降,必须对变压器及时补油。五是检查接地连接的可靠性,如果出现松动,必须对其紧固。六是检查高、低压的接线连接是否牢靠,如果出现变色,局部过热,应立即对变压器停止运行,在做好安全措施后,进行紧固。七是分相检查运行中配电变压器的三相电压,是否在额定电压值的范围内运行,如果电压偏低,应将无功补偿的电容器投入运行,或是调整变压器的分接开关的档位。八是经常对变压器的温度表进行查看,变压器运行温度是否过高,如果温度过高,应采取给变压器降温或限负荷的方法。
(5)接地电阻超标,遭受雷击。
配电变压器雷击损坏主要原因是由于避雷器失效或接地不良而引起的,必须在配电变压器的高、低压侧配置合格的避雷器;一是定期测量避雷器接地电阻,R地≤4Ω,超标及时整改。二是每年雷雨季节前,要安排避雷器的试验,若是试验不合格者,应立即更换。
3.配电变压器运行工况监督方法
运行中的配电变压器,用“看、测、听、闻”这四种方法
(1)“看”的方法
①“看”变压器的大盖、套管、油位计、排油阀、分接开关等,其密封的良好性,有无渗漏油现象。高、低压瓷套管有无裂纹和放电闪络的痕迹。
②“看”油位和油色:油位是否正常。如偏高,变压器运行带负荷后,随着油温的上升,油从油枕的呼吸器处溢出;如偏低,对变压器的绝缘和散热作用会降低,变压器可靠运行受到影响,缺油量较大时变压器会被烧坏。再“看”油有没有变颜色,如果颜色变重了,则需要更换变压器油了。
(2)“测”量(试)的方法
①“测”量变压器绕组对地绝缘电阻和绕组间的绝缘电阻(选用1000~2500V兆欧表),应符合表—2的规定:
②“测”量变压器的接地电阻、避雷器的接地电阻,其阻值在规定的范围内。
(3)“听”的方法
用一节绝缘操作棒一端接触配电变压器的外壳,在另一端用耳听变压器运行中的声音:
①“听”到变压器发出均匀且连续 “嗡嗡”的声音,这是交流电通过线圈时产生的电磁力吸引硅钢片与变压器自身的振动而发出的响声,变压器运行正常。。
②“听”到变压器发出“啾、啾、啾”的声音,有时还造成高压熔丝熔断,这是分接开关未到位,应停电把分接开关重合到位。
③“听”到变压器发出的“嗡嗡”声音忽高忽低,无其它杂音,这是变压器过载运行引起的。应采取限制负荷的方法,保证配电变压器在规定的负荷范围内运行;若是负荷增长了,应考虑配电变压器增容。
④“听”到变压器发出“轰轰”声音,这常是因变压器低压侧的架空线发生接地引起的。
(4)“闻”是靠人的嗅觉功能,“闻”运行中的变压器及周围,有无烧皮子的味道或其他异味,若有异常的味道,必须查清异味的来源。
4.结束语
配电变压器安全、可靠、经济且长周期运行,是与精心维护工作分不开的,定期维护是保证变压器稳定运行的基本保障,避免配电变压器烧毁事故的发生。