七、液化石油气罐的防火间距(一)液化石油气储罐之间的防火间距,不宜小于相邻较大罐的直径。数个储罐总容积超过3000m~3时应分组布置,组内储罐宜采用单排布置,组与组间的防火间距不宜小于20m。当总容积不超过3000m~3,单罐容积不超过1000m~3时可采用双排布置。(二)液化石化油气储罐或罐区与建筑物、堆
VII, fire liquefied petroleum gas tank spacing (A) liquefied petroleum gas tank fire between the spacing should not be less than the adjacent larger tank diameter. A number of the total tank volume of more than 3000m ~ 3 should be arranged in groups, the storage tank should be used within a single row arrangement, group and group fire prevention spacing should not be less than 20m. When the total volume does not exceed 3000m ~ 3, the single tank volume does not exceed 1000m ~ 3 can be double row layout. (B) liquefied petroleum gas tank or tank farm and buildings, piles