针对辽通公司热电分公司在十一五期间两台循环流化床(CFB)锅炉床温高、炉内温度不均、稀相区灰浓度低等问题.从回料器配风、入炉煤粒度、总风量、流化风、入炉煤粒度床压等方面进行了燃烧调整试验。结果表明。通过减少回料器进料侧风量和入炉煤粒度、调节一次风和二次风量的配比等措施,可使平均床温由调整前的990℃降至920~930℃,效果显著。
In view of the problems of high bed temperature, uneven temperature in the furnace and low concentration of ash in the dilute phase in the two circulating fluidized bed (CFB) boilers of Liao Tong Thermal Power Branch during the 11th five-year plan period, Coal particle size, total air flow, fluidized air, into the coal bed pressure and other aspects of the combustion adjustment test. The results show. The average bed temperature can be reduced from 990 ℃ before adjustment to 920 ~ 930 ℃ by reducing the feed air volume on the feed back side and the particle size of the feed coal, and adjusting the ratio of the primary air to the secondary air volume.