我单位一台作为除尘风机用的225kW交流异步电动机,型号JS126-4,△接法,绕组内部并头,4极,额定电流398A,重量1.5t。因故停开数月,当需运行作例行检查时,用500V兆欧表测量电机绕组对地绝缘电阻力0,用MF47型万用表R×100档测量绝缘电阻力800Ω。经检查是受潮所致。按常规做法,需拆下烘干检修。由于此电机体积大,自重重,相连设备及电机拆装都不便,而且也没有这么大的烘箱,检修时间也较长。
I unit as a dedusting fan with 225kW AC induction motor, model JS126-4, △ connection, the winding internal and head, 4 pole, rated current 398A, weight 1.5t. For some reason, it should be parked for several months. When it needs to be run for routine inspection, measure the insulation resistance of the motor winding to ground using a 500V megger, and measure the insulation resistance of 800Ω using the Rf100 MF47 multimeter. After checking is due to damp. According to normal practice, remove the need for drying overhaul. Due to the large motor volume, heavy weight, connected equipment and motor disassembly are inconvenient, but also not so big oven, overhaul time is longer.